H07V-R/H05V-R Electrical wire

450/750V H07V-R (CU/PVC)

300/500V H05V-R (CU/PVC)

Standard: IEC 60227, VDE-0281 Part-3

Construction:

Bare Copper Conductor, PVC Insulation

Application:

For building wire installed in conduit in dry location and inter wiring in switchboard and control panel.

Special Features on Request:

• Fire Resistance

• Oil Resistance

• Flame Retardant Cat. A, B, C

• Flame Retardant Non Category

Standard Packing:

• 1.5 - 16 mm2 supplied in coil with 100 meters

• 25 - 400 2 supplied in wooden drum with 1000 meters

Technical Character:

Conductor: Strand Copper, class 2

Test Voltage: H07V-R: 2500V, H05V-R: 2000V

Working Temperature:-5-70 º C

Max. Conductor temperature: 70 º C

Short-circuit max. Conductor temperature:160°C

Insulation resistance: 10 MΩ x km

Cable Parameter:

No. of Cores x Nominal Cross Sectional Area

Nominal Thickness of Insulation

Nominal Overall Diameter

Nominal Weight

# x mm^2

mm

mm

kg/km

H05V-R

1 x 0.5

0.6

2.2

9

1 x 0.75

0.6

2.4

12

1 x 1

0.6

2.6

15

H07V-R

1 x 1.5

0.7

3

23

1 x 2.5

0.8

3.6

35

1 x 4

0.8

4.2

51

1 x 6

0.8

4.7

71

1 x 10

1

6.1

120

1 x 16

1

7.2

170

1 x 25

1.2

8.4

260

1 x 35

1.2

9.5

350

1 x 50

1.4

11.3

480

1 x 70

1,4

12.6

680

1 x 95

1,6

14.7

930

1 x 120

1,6

16.2

1160

1 x 150

1,8

18.1

1430

1 x 185

2,0

20.2

1780

1 x 240

2,2

22.9

2360

1 x 300

2.4

24.5

2940

1 x 400

2.6

27.5

3740


H07V-R/H05V-R Electrical wire