300/500V H05V2-K (CU/PVC)
450/750V H07V2-K (CU/PVC)
Standard: IEC 60227, VDE-0281 Part-7
Construction:
Bare Copper Conductor, PVC Insulation
These special heat-resistant flexible single-conductor hook-up wires are ideal for use in power current installation, switch cabinets, motors and transformers which are subject to direct contact with high temperature (e.g. varnishing machines and drying towers etc.). These are also suitable for inside wiring of electrical equipments such as lighting and heating apparatus.
Special Features on Request:
• Fire Resistance
• Oil Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
Standard Packing:
• 1.5 - 16 mm2 supplied in coil with 100 meters
• 25 - 400 2 supplied in wooden drum with 1000 meters
Technical Character:
Conductor: Flexible Copper conductor, class 5
Working voltage: 300/500v (H05V2-K)/ 450/750v (H07V2-K)
Test Voltage: 2000v (H05V2-K)/ 2500v (H07V2-K)
Working Temperature: 0-90 º C
Max. Conductor temperature: 90º C
Short-circuit max. Conductor temperature:160°C
Insulation resistance: 10 MΩ x km
Cable Parameter:
|
No. of Cores x Nominal Cross Sectional Area |
Nominal Thickness of Insulation |
Nominal Overall Diameter |
Minimum Insulation Resistance At 70ºC |
Nominal Weight |
|
No x mm² |
mm |
mm |
MΩ/km |
kg/km |
|
H05V2-K |
||||
|
1 x 0.5 |
0.6 |
2.5 |
0.013 |
8.7 |
|
1 x 0.75 |
0.6 |
2.7 |
0.012 |
11.9 |
|
1 x 1 |
0.6 |
2.8 |
0.01 |
14 |
|
H07V2-K |
||||
|
1 x 1.5 |
0,7 |
3.4 |
0.01 |
20 |
|
1 x 2.5 |
0,8 |
4.1 |
0.009 |
33.3 |
|
1 x 4 |
0,8 |
4.8 |
0.007 |
48.3 |
|
1 x 6 |
0,8 |
5.3 |
0.006 |
68.5 |
|
1 x 10 |
1,0 |
6.8 |
0.0056 |
115 |
|
1 x 16 |
1,0 |
8.1 |
0.0046 |
170 |
|
1 x 25 |
1,2 |
10.2 |
0.0044 |
270 |
|
1 x 35 |
1,2 |
11.7 |
0.0038 |
367 |
|
1 x 50 |
1,4 |
13.9 |
0.0037 |
520 |
|
1 x 70 |
1,4 |
16 |
0.0032 |
729 |
|
1 x 95 |
1,6 |
18.2 |
0.0032 |
962 |
|
1 x 120 |
1,6 |
20.2 |
0.0029 |
1235 |
|
1 x 150 |
1,8 |
22.5 |
0.0029 |
1523 |
|
1 x 185 |
2,0 |
24.9 |
0.0029 |
1850 |
|
1 x 240 |
2,2 |
28.4 |
0.0028 |
2430 |