Application:
These cables are suitable For building wire installed in conduit in dry location and inter wiring in switchboard and control panel.
Special Features on Request:
• Fire Resistance
• Oil Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
Standard Packing:
• 1.5 - 16 mm2 supplied in coil with 100 meters
• 25 - 400 2 supplied in wooden drum with 1000 meters
Technical Character:
Conductor: Strand Aluminium, class 2
Working Voltage: 450/750V
Test Voltage: 2500V
Working Temperature:0-70 º C
Max. Conductor temperature: 70 º C
Short-circuit max. Conductor temperature:150°C
Insulation resistance: 10 MΩ x km
Cable Diameter
|
Nominal Cross Sectional Area |
Nominal Thickness of Insulation |
Nominal Overall Diameter |
Nominal Copper Weight |
Nominal Weight |
|
mm² |
mm |
mm |
MΩ/KM |
KG/KM |
|
10 |
1 |
6.2 |
0.0065 |
54 |
|
16 |
1 |
7.3 |
0.005 |
77 |
|
25 |
1.2 |
9 |
0.005 |
117 |
|
35 |
1.2 |
10.1 |
0.0045 |
153 |
|
50 |
1.4 |
12.2 |
0.0045 |
210 |
|
70 |
1.4 |
13.7 |
0.0035 |
271 |
|
95 |
1.6 |
16 |
0.0035 |
374 |
|
120 |
1.6 |
17.7 |
0.0032 |
452 |
|
150 |
1.8 |
19.7 |
0.0032 |
559 |
|
185 |
2 |
22 |
0.0032 |
696 |
|
240 |
2.2 |
25.1 |
0.0032 |
903 |
|
300 |
2.4 |
27.9 |
0.003 |
1,119 |
|
400 |
2.6 |
31.3 |
0.0028 |
1,410 |