N2XSRY 3.6/6kv voltage underground 300mm single core cable

3.6/6kv Power Cables Single Core Cables to IEC 60502 Standards
IEC 60502 Part 2

3.6/6kv Power Cables Single Core Cables to IEC 60502 Application
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

3.6/6kv Power Cables Single Core Cables to IEC 60502 Construction

Conductor: Plain annealed copper or aluminium complying with IEC 60228 class 1 or 2. 
Conductor Screen: The conductor screen consists of an extruded layer of non metallic, semi-conducting compound firmly bonded to the insulation to exclude all air voids.
Insulation:
 Insulation is of polyvinyl chloride (PVC) intended for 1.8/3KV and 3.6/6KV cables, cross-linked polyethylene compound (XLPE)

Insulaton Screen:  It will consist of a layer of copper wires applied helically with overlap over insulation screen. Other combinations of metallic screens base on customs demand.
Separation Sheath (for armoured cable): The separation sheath comprises a layer of extruded PVC, PE or LSZH, applied under the armour .
Lapped Bedding : The lapped bedding consists of Polyester non woven fabrics .The thickness is1.5mm
Armour (for armoured cable): The armour consists of round galvanized steel wire armour applied helically over an extruded separation sheath.
Outer Sheath: Outer sheath comprises a layer of extruded thermoplastic compound (PVC, PE or LSZH can be offered as an option.) or elastomeric compound (polychlorprene CSP or chlorosulfonated PE).

Installation and operation condition of cable
Operating Temperature: up to 70°C (PVC insulation); up to 90°C (XLPE or EPR insulation)
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature( 5 seconds maximum duration ): 140-160°C (PVC insulation);
250°C (XLPE)
Bending Radius: 12 x OD
Current Rating Conditions:
Ground Temperature: 20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W

Rated Voltage Uo/U Operating Voltage (Um) Testing Voltage
 (rms)
3.6/6KV 7.2KV 12.5KV  

 

3.6/6KV (Um=12KV) Power Cables Single Core Cables Dimensional Data:

Nom.Cross-Section Area   Unarmoured Cables Steel Wire Armoured Cables
Nom.Insulation Thickness Copper Tape Thickness Copper Wire Screen Area*  Nom.Sheath Thickness Approx.Overall Diameter Approx.Weight Nom.Bedding Thickness Armour Wire Size Nom.Sheath Thickness Approx.Overall Diameter Approx.Weight
CU AL CU AL
mm2 mm mm mm2 mm mm kg/km mm mm mm mm kg/km
16 2.5 0.1 16 1.8 16 390 290 1.2 1.6 1.8 22 680 580
25 2.5 0.1 16 1.8 18 500 340 1.2 1.6 1.8 23 810 660
35 2.5 0.1 16 1.8 19 610 400 1.2 1.6 1.8 24 940 730
50 2.5 0.1 16 1.8 20 750 450 1.2 1.6 1.8 26 1100 810
70 2.5 0.1 16 1.8 22 970 550 1.2 1.6 1.8 27 1350 930
95 2.5 0.1 16 1.8 23 1250 660 1.2 1.6 1.9 29 1670 1080
120 2.5 0.1 16 1.8 25 1500 760 1.2 1.6 1.9 31 1950 1200
150 2.5 0.1 25 1.8 26 1790 860 1.2 1.6 2 32 2270 1350
185 2.5 0.1 25 1.8 28 2150 1000 1.2 2 2.1 35 2770 1620
240 2.6 0.1 25 1.9 31 2770 1250 1.2 2 2.2 38 3440 1930
300 2.8 0.1 25 2 34 3400 1500 1.2 2 2.2 41 4120 2210
400 3 0.1 35 2.1 38 4280 1850 1.3 2.5 2.4 46 5250 2820
500 3.2 0.1 35 2.1 41.5 5325 2240 1.4 2.5 2.6 50 6520 3520
630 3.2 0.1 35 2.2 45.3 6745 2750 1.5 2.5 2.7 56 7960 4020
800 3.2 0.1 50 2.4 49.9 8290 3310 1.5 2.5 2.8 59 9660 4820
1000 3.2 0.1 50 2.5 54.2 10255 3990 1.6 2.5 3 63 11690 5540
N2XSRY 3.6/6kv voltage underground 300mm single core cable