Construction:
Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed
Standards:
IEC60502-2
Application:
These power are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.
Special Features on Request
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
Technical Data:
Conductor: Copper conductors shall be stranded (class 2) and aluminium conductors shall be either solid or stranded (class 2).
Operating Temperature:up to 90°C
Short Circuit Temperature ( 5 seconds maximum duration ): 250°C
Bending Radius: 20 x OD
Nominal /Operating /Testing Voltages
Rated Voltage Uo/U |
Operating Voltage (Um) |
Testing Voltage (rms) |
1.8/3KV |
3.6KV |
6.5KV |
3.6/6KV |
7.2KV |
12.5KV |
6/10KV |
12KV |
21KV |
8.7/15KV |
17.5KV |
30.5KV |
12/20KV |
24KV |
42KV |
18/30KV |
36KV |
63KV |
21/35KV |
42KV |
73.5(53)*KV |
26/35KV |
42KV |
91(65)*KV |
N2XSEBY 3 x (25-300) mm² 3.6/6kV Physical Data:
Nom. Cross Section Area |
Overall Diameter |
Cable Weight |
|
approx. |
approx. |
mm² |
mm |
kg/km |
25 |
38.5 |
2,417 |
35 |
41 |
2,865 |
50 |
44 |
3,391 |
70 |
48 |
4,272 |
95 |
51.5 |
5,266 |
120 |
55.5 |
6,232 |
150 |
59 |
7,271 |
185 |
63 |
8,585 |
240 |
69 |
10,679 |
300 |
75.5 |
12,965 |
