Construction:
Stranded Aluminum Conductor Class 2, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed
Standards:
IEC60502-2
Application:
These power are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations
Technical Data:
Conductor: Stranded aluminium conductors (class 2).
Operating Temperature: up to 90°C
Short Circuit Temperature ( 5 seconds maximum duration ): 250°C
Bending Radius: 20 x OD
Nominal /Operating /Testing Voltages
Rated Voltage Uo/U |
Operating Voltage (Um) |
Testing Voltage (rms) |
1.8/3KV |
3.6KV |
6.5KV |
3.6/6KV |
7.2KV |
12.5KV |
6/10KV |
12KV |
21KV |
8.7/15KV |
17.5KV |
30.5KV |
12/20KV |
24KV |
42KV |
18/30KV |
36KV |
63KV |
21/35KV |
42KV |
73.5(53)*KV |
26/35KV |
42KV |
91(65)*KV |
NA2XSERY 3 x (25-300) mm² 3.6/6 kV Cable Paramter:
Al / XLPE / CTS / PVC / SWA / PVC
Nom. Cross Section Area |
Approx. Overall Diameter |
Approx.Cable Weight |
mm² |
mm |
kg/km |
25 |
40.5 |
2589 |
35 |
43.5 |
2993 |
50 |
48 |
3705 |
70 |
52 |
4324 |
95 |
56 |
4947 |
120 |
59.5 |
5541 |
150 |
62.5 |
6126 |
185 |
67 |
6886 |
240 |
72.5 |
8037 |
300 |
80 |
10170 |
NA2XSERY 3 x (25-300) mm² 3.6/6 kV Electrical Data:
Conductor |
|||
Nom. Cross Section Area |
DC Resistance at 20°C |
AC Resistance at 90°C |
|
(mm²) |
Max. (Ω/km) |
Max. (Ω/km) |
|
25 |
1.2 |
1.539 |
|
35 |
0.868 |
1.113 |
|
50 |
0.641 |
0.822 |
|
70 |
0.443 |
0.568 |
|
95 |
0.32 |
0.411 |
|
120 |
0.253 |
0.325 |
|
150 |
0.206 |
0.265 |
|
185 |
0.164 |
0.212 |
|
240 |
0.125 |
0.162 |
|
300 |
0.1 |
0.13 |