NA2XSERY 3.6/6kv famous importer xlpe power 3 core cable

Construction:

Stranded Aluminum Conductor Class 2, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed

Standards:

 IEC60502-2

Application:

These power are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations

Technical Data:

Conductor: Stranded aluminium conductors  (class 2).

Operating Temperature: up to 90°C

Short Circuit Temperature ( 5 seconds maximum duration ): 250°C

Bending Radius: 20 x OD

Nominal /Operating /Testing Voltages

Rated Voltage Uo/U

Operating Voltage

(Um)

Testing Voltage (rms)

1.8/3KV

3.6KV

6.5KV

3.6/6KV

7.2KV

12.5KV

6/10KV

12KV

21KV

8.7/15KV

17.5KV

30.5KV

12/20KV

24KV

42KV

18/30KV

36KV

63KV

21/35KV

42KV

73.5(53)*KV

26/35KV

42KV

91(65)*KV

NA2XSERY 3 x (25-300) mm² 3.6/6 kV Cable Paramter:

Al / XLPE / CTS / PVC / SWA / PVC

Nom. Cross Section Area

Approx. Overall Diameter

Approx.Cable Weight

mm²

mm

kg/km

25

40.5

2589

35

43.5

2993

50

48

3705

70

52

4324

95

56

4947

120

59.5

5541

150

62.5

6126

185

67

6886

240

72.5

8037

300

80

10170

 

NA2XSERY 3 x (25-300) mm² 3.6/6 kV Electrical Data:

 

Conductor

 

Nom. Cross Section Area

DC Resistance at 20°C

AC Resistance at 90°C

 
 

(mm²)

Max. (Ω/km)

Max. (Ω/km)

 

25

1.2

1.539

 

35

0.868

1.113

 

50

0.641

0.822

 

70

0.443

0.568

 

95

0.32

0.411

 

120

0.253

0.325

 

150

0.206

0.265

 

185

0.164

0.212

 

240

0.125

0.162

 

300

0.1

0.13

 

 

 

NA2XSERY 3.6/6kv famous importer xlpe power 3 core cable