Na2xsy 240mm 35mm underground high voltage aluminum power cable

3.6/6kv Power Cables Single Core Cables to IEC 60502 Standards
IEC 60502 Part 2

3.6/6kv Power Cables Single Core Cables to IEC 60502 Application
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

3.6/6kv Power Cables Single Core Cables to IEC 60502 Construction

Conductor: Stranded aluminium conductor Class 2 complying with IEC 60228 class 1 or 2. 
Conductor Screen: The conductor screen consists of an extruded layer of non metallic, semi-conducting compound firmly bonded to the insulation to exclude all air voids.
Insulation:
 XLPE

Insulaton Screen: Double copper tape and Copper wires applied helically with copper tape.
Lapped Bedding : The lapped bedding consists of Polyester non woven fabrics .
Outer Sheath: PVC, PE or LSZH can be offered as an option.) 

Installation and operation condition of cable
Operating Temperature: up to 90°C 
Short Circuit Temperature( 5 seconds maximum duration ): 250°C
Bending Radius: 12 x OD
Current Rating Conditions:
Ground Temperature: 
20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m

Thermal Resistance of Soil: 1.5K•m/W

Rated Voltage Uo/U Operating Voltage (Um) Testing Voltage
 (rms)
3.6/6KV 7.2KV 12.5KV  

 

3.6/6KV (Um=12KV) Power Cables Single Core Cables Dimensional Data:

Al / XLPE/ CTS / PVC

Nom. Cross Section Area

Approx. Overall Diameter

Approx.Cable Weight

mm²

mm

kg/km

1x25

16.9

374

1x35

18.1

431

1x50

19.1

492

1x70

21

593

1x95

23

706

1x120

24.5

807

1x150

25.5

867

1x185

27.5

1018

1x240

30

1243

1x300

32.5

1474

1x400

36.5

1777

1x500

40

2178

1x630

45

2700

 

 
3.6/6KV (Um=12KV) Power Cables Single Core Cables Electrical Data:

Conductor

Inductance

 

Nom. Cross Section Area

DC Resistance at 20°C

AC Resistance at 90°C

Trefoilformation

Flatformation

 
 

(mm²)

Max. (Ω/km)

Max. (Ω/km)

(mH/km)

(mH/km)

 

1x25

1.2

1.539

0.399

0.445

 

1x35

0.868

1.113

0.376

0.422

 

1x50

0.641

0.822

0.36

0.407

 

1x70

0.443

0.568

0.339

0.385

 

1x95

0.32

0.411

0.324

0.37

 

1x120

0.253

0.325

0.313

0.359

 

1x150

0.206

0.265

0.303

0.35

 

1x185

0.164

0.211

0.295

0.341

 

1x240

0.125

0.162

0.288

0.335

 

1x300

0.1

0.13

0.283

0.33

 

1x400

0.0778

0.102

0.277

0.323

 

1x500

0.0605

0.081

0.273

0.319

 

1x630

0.0469

0.064

0.264

0.31

 
 

 

Na2xsy 240mm 35mm underground high voltage aluminum power cable