Construction:
Stranded Aluminum Conductor Class 2, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed
Standards:
IEC60502-2
Application:
These power are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.
Special Features on Request
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
Technical Data:
Conductor: Stranded aluminium conductors (class 2).
Operating Temperature: up to 70°C (PVC insulation); up to 90°C (XLPE insulation)
Short Circuit Temperature ( 5 seconds maximum duration ): 140-160°C (PVC insulation);
250°C (XLPE insulation)
Bending Radius: 20 x OD
Nominal /Operating /Testing Voltages
Rated Voltage Uo/U |
Operating Voltage (Um) |
Testing Voltage (rms) |
1.8/3KV |
3.6KV |
6.5KV |
3.6/6KV |
7.2KV |
12.5KV |
6/10KV |
12KV |
21KV |
8.7/15KV |
17.5KV |
30.5KV |
12/20KV |
24KV |
42KV |
18/30KV |
36KV |
63KV |
21/35KV |
42KV |
73.5(53)*KV |
26/35KV |
42KV |
91(65)*KV |
NA2XSEB(AL)Y 3 x (25-300) mm2 3.6/6 kV Cable Parameter
Al / XLPE/ CTS / PVC / ATA / PVC
Nom. Cross Section Area |
Approx. Overall Diameter |
Approx.Cable Weight |
mm² |
mm |
kg/km |
3x25 |
36.5 |
1380 |
3x35 |
39.5 |
1620 |
3x50 |
42 |
1908 |
3x70 |
46.5 |
2322 |
3x95 |
50 |
2781 |
3x120 |
54 |
3252 |
3x150 |
57 |
3673 |
3x185 |
61.5 |
4268 |
3x240 |
67 |
5172 |
3x300 |
73 |
6226 |
NA2XSEB(AL)Y 3 x (25-300) mm2 3.6/6 kV Electrical Data
Conductor |
|||
Nom. Cross Section Area |
DC Resistance at 20°C |
AC Resistance at 90°C |
|
(mm²) |
Max. (Ω/km) |
Max. (Ω/km) |
|
3x25 |
1.2 |
1.539 |
|
3x35 |
0.868 |
1.113 |
|
3x50 |
0.641 |
0.822 |
|
3x70 |
0.443 |
0.568 |
|
3x95 |
0.32 |
0.411 |
|
3x120 |
0.253 |
0.325 |
|
3x150 |
0.206 |
0.265 |
|
3x185 |
0.164 |
0.212 |
|
3x240 |
0.125 |
0.162 |
|
3x300 |
0.1 |
0.13 |