Re-2xy Sway cu conductor xlpe insulation instrumentation cable

Structure:
Copper Conductor, XLPE Insulated, Aluminium/polyester Tape Overall Screen, Galvanized Steel Wire Armor, PVC Sheathed
Standards:
BS EN 50288-7,,IEC 60502-1

APPLICATION:
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Suitable fordirect burial applications.

PhysIcal and Thermal Properties
Conductor: Annealed copper solid Class 1 or plain copper stranded Class 2
Voltage Rating: 300V/500V
Test Voltage:1200V/2000V
Temperature range During operation (fixed state): -30°C - +90°C
Temperature range During Installation (Mobile state): -5°C - +50°C
Minimum bending radius:10 X Overall Diameter

 

Electrical Data:

Conductor Insulation Mutual Capacitance
Nominal Cross Section Resistance Resistance
at 20°C at 20°C
   
  max. min. max.
mm2 ohm/km Mohm.km  pF/m
     
0.5 36.7 5000 115
0.75 25 5000 115
1 18.5 5000 115
1.5 12.3 5000 115
2.5 7.4 5000 115

 

Cable Parameter:

No. of Core x1xCross Section Nominal Insulation Thickness Nominal Inner Sheath Thickness Nominal Overall Diameter Over Inner Sheath Nominal Armour Wire Diameter Nominal Outer Sheath Thickness Nominal Overall Diameter Approx. Weight
No.x1xmm2 mm mm mm mm mm mm kg/km
0.5mm2, Multicore
2x1x0.5 0.55 0.9 6.2 0.9 1.3 10.6 210
3x1x0.5 0.55 0.9 6.5 0.9 1.3 10.9 230
4x1x0.5 0.55 0.9 7 0.9 1.3 11.4 253
5x1x0.5 0.55 0.9 7.6 0.9 1.3 12 283
8x1x0.5 0.55 1 9.1 0.9 1.4 13.7 344
10x1x0.5 0.55 1 10.4 0.9 1.4 15 399
12x1x0.5 0.55 1 10.7 0.9 1.4 15.3 442
14x1x0.5 0.55 1 11.3 0.9 1.4 15.9 474
16x1x0.5 0.55 1.1 11.8 0.9 1.4 16.4 505
20x1x0.5 0.55 1.1 13.3 0.9 1.5 18.1 569
24x1x0.5 0.55 1.1 14.7 0.9 1.5 19.5 642
27x1x0.5 0.55 1.2 15 0.9 1.5 19.8 808
30x1x0.5 0.55 1.2 15.7 0.9 1.5 20.5 848
37x1x0.5 0.55 1.2 16.9 0.9 1.6 21.9 963
Re-2xy Sway cu conductor xlpe insulation instrumentation cable