Multi core flexible twist pair instrumentation cables

Multi core flexible twist pair instrumentation cables Structure:
Copper Conductor, PVC Insulated, braid Copper wire (CWB) screen, PVC Sheathed Instrumentation cable
Multi core flexible twist pair instrumentation cables Standards:
BS5308,,IEC 60502-1

Multi core flexible twist pair instrumentation cables APPLICATION:
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Not suitable for direct burial applications.

Multi core flexible twist pair instrumentation cables PhysIcal and Thermal Properties

Conductor: plain stranded copper conductor Class 2 or class 5
Voltage Rating: 300V/500V
Test Voltage:1200V/2000V
Temperature range During operation (fixed state): -30°C - +70°C
Temperature range During Installation (Mobile state): -5°C - +50°C
Minimum bending radius: 7.5 X Overall Diameter

Electrical Data:

Conductor Insulation Mutual Capacitance
Nominal Cross Section Resistance Resistance
at 20°C at 20°C
   
  max. min. max.
mm2 ohm/km Mohm.km  pF/m
     
0.5 36.7 5000 115
0.75 25 5000 115
1 18.5 5000 115
1.5 12.3 5000 115

 

Cable Parameter:

No.x2xCross Section Nominal Overall Diameter Approx. Weight
No.x2xmm2 Kg/km Kg/km
0.5mm2, Multipair
1x2x0.50 8.3 110
2x2x0.50 10.7 143
4x2x0.50 11.1 159
5x2x0.50 11.9 181
6x2x0.50 13.6 230
8x2x0.50 14.2 264
12x2x0.50 16.4 343
16x2x0.50 18.2 418
20x2x0.50 19.7 487
24x2x0.50 21.1 557
Multi core flexible twist pair instrumentation cables