Structure:
Plain Copper Conductor, PVC Insulated, Aluminium/polyester Tape Overall Screen, PVC Sheathed
Standards:
BS5308,,IEC 60502-1
APPLICATION:
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Suitable fordirect burial applications.
PhysIcal and Thermal Properties
Conductor: plain copper stranded Class 2 or Class 5
Voltage Rating: 300V/500V
Test Voltage:1200V/2000V
Temperature range During operation (fixed state): -30°C - +70°C
Temperature range During Installation (Mobile state): -5°C - +50°C
Minimum bending radius:10 X Overall Diameter
Electrical Data:
| Conductor | Insulation | Mutual Capacitance | |
| Nominal Cross Section | Resistance | Resistance | |
| at 20°C | at 20°C | ||
| max. | min. | max. | |
| mm2 | ohm/km | Mohm.km | pF/m |
| 0.5 | 36.7 | 5000 | 115 |
| 0.75 | 25 | 5000 | 115 |
| 1 | 18.5 | 5000 | 115 |
| 1.5 | 12.3 | 5000 | 115 |
| 2.5 | 7.4 | 5000 | 115 |
Cable Parameter:
|
No. of Pairs x2xCross Section |
Nominal Overall Diameter |
Approx. Weight |
|
No.x2xmm2 |
mm |
kg/km |
|
1x2x0.50 |
5.2 |
38 |
|
2x2x0.5 |
7.6 |
66 |
|
4x2x0.5 |
8.8 |
98 |
|
5x2x0.5 |
9.8 |
112 |
|
6x2x0.5 |
10.6 |
133 |
|
8x2x0.5 |
11.3 |
161 |
|
10x2x0.5 |
12.9 |
200 |
|
1x2x0.75 |
5.6 |
49 |
|
2x2x0.75 |
8.5 |
87 |
|
3x2x0.75 |
10 |
122 |
|
4x2x0.75 |
10.9 |
154 |
|
5x2x0.75 |
11.8 |
174 |
|
8x2x0.75 |
12.8 |
213 |
|
10x2x0.75 |
14.5 |
266 |
|
1x2x1.0 |
6.3 |
56 |
|
2x2x1.0 |
9.2 |
101 |
|
3x2x1.0 |
10.9 |
157 |
|
4x2x1.0 |
11.9 |
194 |
|
5x2x1.0 |
13 |
223 |
|
8x2x1.0 |
14 |
272 |
|
10x2x1.0 |
15.9 |
334 |
|
1x2x1.5 |
7.1 |
71 |
|
2x2x1.5 |
10.8 |
139 |
|
3x2x1.5 |
12.7 |
214 |
|
4x2x1.5 |
14 |
259 |
|
5x2x1.5 |
15.2 |
305 |
|
8x2x1.5 |
16.4 |
385 |
|
10x2x1.5 |
18.8 |
460 |