6491B/H07Z-R electrical cords cable the wire season online box

Cable Construction:
Class 2 Stranded copper conductors, LSOH Insulation
Cable Application

The cable Suitable for use in conduit and for fixed, protected installation.For installations where fire, smoke emission and toxic fume create a potential risk to life and equipment

Cable Standards
BS EN 50525-3-41 ,IEC 60227 EN 50265-2-1, IEC 60332.1 , EN 50268 / IEC 61034, EN 50267-2-2, IEC 60754-2
Cable Technical Character:
Conductor:Stranded Copper Conductor, class 2
Working voltage:450/750KV
Test Voltage:2500V
Working Temperature:0-90º C
Bending Radiu:
 6 x overall diameter
Max. Conductor temperature: 90 º C
Short-circuit max. Conductor temperature:250°C
Insulation resistance: 10 MΩ x km

 

No.  x Area

 Thickness 

 Overall Diameter

Weight

# x mm²

mm

mm

kg/km

1 x 1.5

0.7

2.8-3.5

24

1 x 2.5

0.8

3.4-4.3

35

1 x 4

0.8

3.9-4.9

51

1 x 6

0.8

4.4-5.5

71

1 x 10

1

5.7-7.1

118

1 x 16

1

6.7-8.4

180

1 x 25

1.2

8.4-10.6

278

1 x 35

1.2

9.7-12.1

375

1 x 50

1.4

11.5-14.4

560

1 x 70

1.4

13.2-16.6

780

1 x 95

1.6

15.1-18.8

952

1 x 120

1.6

16.7-20.9

1200

1 x 150

1.8

18.6-23.3

1505

1 x 185

2

20.6-25.8

1845

6491B/H07Z-R electrical cords cable the wire season online box