Construction:
Bare Copper Conductor, PVC
Insulation
Application: For building wire installed in conduit in dry location and inter wiring in
switchboard and
control panel.
Special Features on Request:
• Fire Resistance
• Oil Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant
Non Category
Standard Packing:
• 1.5 - 16 mm2 supplied in coil with
100 meters
• 25 - 400 2 supplied in wooden
drum with 1000 meters
Technical Character:
Conductor: Flexible Cord, class 5
Test Voltage: H07V-K: 2500V, H05V-K: 2000V
Working Temperature:-5-70 º
C
Max. Conductor temperature: 70 º
C
Short-circuit max. Conductor
temperature:160°C
Cable Parameter:
No. of Cores x Nominal Cross Sectional Area
Nominal Thickness of Insulation
Nominal Overall Diameter
Minimum Insulation Resistance At 70ºC
Nominal Weight
No x mm²
mm
mm
MΩ/km
kg/km
H05V-K
1 x 0.5
0.6
2.1
0.015
10
1 x 0.75
0.6
2.4
0.013
13
1 x 1
0.6
2.6
0.012
15
H07V-K
1 x 1.5
0,7
3.1
0.11
20
1 x 2.5
0,8
3.6
0.1
31
1 x 4
0,8
4.3
0.009
48
1 x 6
0,8
4.9
0.0084
69
1 x 10
1,0
6.4
0.0072
121
1 x 16
1,0
8.1
0.0062
211
1 x 25
1,2
9.8
0.0058
303
1 x 35
1,2
11.1
0.0052
417
1 x 50
1,4
13.1
0.0051
539
1 x 70
1,4
15.5
0.0045
730
1 x 95
1,6
17.2
0.004
900
1 x 120
1,6
19.7
0.0032
1135
1 x 150
1,8
21.3
0.0032
1410
1 x 185
2,0
23.4
0.0032
1845
1 x 240
2,2
27.1
0.0032
2270