H07V-K Electrical Wire

Construction:

Bare Copper Conductor, PVC Insulation

Application: For building wire installed in conduit in dry location and inter wiring in switchboard and

control panel.

Special Features on Request:

• Fire Resistance

• Oil Resistance

• Flame Retardant Cat. A, B, C

• Flame Retardant Non Category

Standard Packing:

• 1.5 - 16 mm2 supplied in coil with 100 meters

• 25 - 400 2 supplied in wooden drum with 1000 meters

Technical Character:

Conductor: Flexible Cord, class 5

Test Voltage: H07V-K: 2500V, H05V-K: 2000V

Working Temperature:-5-70 º C

Max. Conductor temperature: 70 º C

Short-circuit max. Conductor temperature:160°C

Insulation resistance: 10 MΩ x km

Cable Parameter:

No. of Cores x Nominal Cross Sectional Area

Nominal Thickness of Insulation

Nominal Overall Diameter

Minimum Insulation Resistance At 70ºC

Nominal Weight

No x mm²

mm

mm

MΩ/km

kg/km

H05V-K

1 x 0.5

0.6

2.1

0.015

10

1 x 0.75

0.6

2.4

0.013

13

1 x 1

0.6

2.6

0.012

15

H07V-K

1 x 1.5

0,7

3.1

0.11

20

1 x 2.5

0,8

3.6

0.1

31

1 x 4

0,8

4.3

0.009

48

1 x 6

0,8

4.9

0.0084

69

1 x 10

1,0

6.4

0.0072

121

1 x 16

1,0

8.1

0.0062

211

1 x 25

1,2

9.8

0.0058

303

1 x 35

1,2

11.1

0.0052

417

1 x 50

1,4

13.1

0.0051

539

1 x 70

1,4

15.5

0.0045

730

1 x 95

1,6

17.2

0.004

900

1 x 120

1,6

19.7

0.0032

1135

1 x 150

1,8

21.3

0.0032

1410

1 x 185

2,0

23.4

0.0032

1845

1 x 240

2,2

27.1

0.0032

2270




H07V-K Electrical Wire