Cable Construction:
Class 2 Stranded copper conductors, LSOH Insulation
Cable Application
The cable Suitable for use in conduit and for fixed, protected installation.For installations where fire, smoke emission and toxic fume create a potential risk to life and equipment
Cable Standards
BS EN 50525-3-41 ,IEC 60227 EN 50265-2-1, IEC 60332.1 , EN 50268 / IEC 61034, EN 50267-2-2, IEC 60754-2
Cable Technical Character:
Conductor:Stranded Copper Conductor, class 2
Working voltage:450/750KV
Test Voltage:2500V
Working Temperature:0-90º C
Bending Radiu: 6 x overall diameter
Max. Conductor temperature: 90 º C
Short-circuit max. Conductor temperature:250°C
Insulation resistance: 10 MΩ x km
|
No. of Cores x Nominal Cross Sectional Area |
Nominal Thickness of Insulation |
Nominal Overall Diameter |
Nominal Weight |
Minimum insulation resistance at 90°C |
|
# x mm² |
mm |
mm |
kg/km |
MΩ·km |
|
2491B(H05Z-R) |
||||
|
1 x 0.5 |
0.6 |
2.1-2.6 |
9 |
0.013 |
|
1 x 0.75 |
0.6 |
2.2-2.8 |
12.4 |
0.011 |
|
1 x 1 |
0.6 |
2.4-2.9 |
15 |
0.01 |
|
6701B(H07Z-R) |
||||
|
1 x 1.5 |
0.7 |
2.8-3.5 |
24 |
0.01 |
|
1 x 2.5 |
0.8 |
3.4-4.3 |
35 |
0.009 |
|
1 x 4 |
0.8 |
3.9-4.9 |
51 |
0.007 |
|
1 x 6 |
0.8 |
4.4-5.5 |
71 |
0.006 |
|
1 x 10 |
1 |
5.7-7.1 |
118 |
0.0056 |
|
1 x 16 |
1 |
6.7-8.4 |
180 |
0.0046 |
|
1 x 25 |
1.2 |
8.4-10.6 |
278 |
0.0044 |
|
1 x 35 |
1.2 |
9.7-12.1 |
375 |
0.0038 |
|
1 x 50 |
1.4 |
11.5-14.4 |
560 |
0.0037 |
|
1 x 70 |
1.4 |
13.2-16.6 |
780 |
0.0032 |
|
1 x 95 |
1.6 |
15.1-18.8 |
952 |
0.0032 |
|
1 x 120 |
1.6 |
16.7-20.9 |
1200 |
0.0029 |
|
1 x 150 |
1.8 |
18.6-23.3 |
1505 |
0.0029 |
|
1 x 185 |
2 |
20.6-25.8 |
1845 |
0.0029 |
|
1 x 240 |
2.2 |
23.5-29.4 |
2400 |
0.0028 |